Load Sharing & Synchronising Control Modules

DSEG8500

Standard Parallel Genset Controller
The DSEG8500 is a parallel genset controller with integral heater designed for complex paralleling applications. The DSEG8500 can be configured to provide paralleling for up to 64 generators on a single site and provides a wide range of high-end features for multiple application environments. The module is configurable for use as a single-set controller or multi-set controller, and can be used with the DSEG8600 configured as a multi-set or mains (utility) controller.
Overall (W x H x D)
248 mm x 182.6 mm x 45.2 mm / 9.77” x 7.19” x 1.78”

Panel Cut-Out (W x H)
220 mm x 160 mm / 8.66” x 6.3”

Maximum Panel Thickness
8 mm / 0.31”

Request a Quote

✕
e -
Please select a product
Please enter a quantity
e +

add another product

Please enter your title
Please enter your first name
Please enter your surname
Please enter your company name
Please select your country
Please enter a delivery County/State
Please enter your email
Please enter your mobile number
Webform URL: Website Option: Webform: Named Distributor: Distributor's Email: Named Reseller: Reseller's Email:


l

Product Highlights

Key Features

Key Features

2 module applications in one product (single-set and multi-set)
Flexible bus segments
Slip sync synchronising control
Advanced multi-set communications (AMSC) link with optional redundancy
Shared virtual inputs, outputs and data via AMSC
Advanced PLC functionality including multi-purpose PIDs
Flexible inputs and outputs
DSENet® Expansion Support
PC configuration using DSE Configuration Suite
Multiple language support
Enhanced 6-line high resolution display with on screen application diagrams
Integrated gasket (IP65 protection)
2 integrated RS485 ports providing Modbus RTU support
Integrated Ethernet port providing Modbus TCP and SNMP v2C support
Data logging of up to 20 parameters
Multi-level pin protected front panel editor
Manual front panel and automatic control modules

Specification

DC Supply

Continuous Voltage Rating
8 V to 35 V DC continuous

Cranking Dropouts
Able to survive 0 V for 100 ms, providing supply was at least 10 V before dropout
and supply recovers to 5 V. This is achieved without the need for internal batteries.
Backlight will not be maintained during cranking.

Maximum Operating Current
700 mA at 12 V, 350 mA at 24 V

Maximum Standby Current
350 mA at 12 V, 190 mA at 24 V

Charge Alternator Excitation / Fail Range
0 V to 35 V

Voltage Measurement

Number
2

Measurement Inputs
3 Phase + Neutral
Single-Set Controller: Generator and Mains (Utility)
Multi-Set Controller: Generator and Bus

Voltage Range
15 V to 415 V Phase to Neutral
25 V to 719 V Phase to Phase

Voltage Accuracy
±0.3 % Phase to Neutral
±0.6 % Phase to Phase

Frequency Range
3.5 Hz to 75 Hz

Frequency Accuracy
±0.01 Hz

Digital Inputs

Number
9

Type
Negative Switching Digital Input

Closed Voltage Threshold
Less than 2.1 V

Open Voltage Threshold
Greater than 6.6 V

Digital Outputs

Number
12

Type
1 Normally Open Volt-Free Contacts
1 Normally Closed Volt-Free Contacts
10 Positive Switching DC Output

Volt-Free Contact Output Rating
5 ADC resistive at 30 VDC
8 AAC resistive at 250 VAC

Positive DC Output Rating Output
A to B (Fuel and Start): 15 ADC at Emergency Stop input supply voltage
Output E to L: 2 ADC at module supply voltage

Communications

USB A
1 Data Storage Port

USB B
1 Programming Port

DSENet®
1 Expansion Port

RS485
2 Fully Isolated RS485 Ports

Ethernet
1 10/100 Ethernet Port

CAN
3 Fully Isolated CAN Ports

Single-Set Controller:
CAN 1 – Engine ECU/ECM
CAN 2 – Not Used
CAN 3 – Not Used

Multi-Set Controller:
CAN 1 – Engine ECU/ECM
CAN 2 – AMSC
CAN 3 – Redundant AMSC

Temperature

Operating Temperature
-40 °C to +70 °C / -40 °F to +158 °F

Storage Temperature
-40 °C to +85 °C / -40 °F to +185 °F

Environmental Testing Standards

Electro-Magnetic Compatibility

BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment

BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment

Electrical Safety

BS EN 61010
Safety of Information Technology Equipment, including Electrical Business Equipment

Temperature

BS EN 60068-2-1
Ab/Ae Cold Test -30 ºC

BS EN 60068-2-2
Bb/Be Dry Heat +70 ºC

Vibration

BS EN 60068-2-6
Ten sweeps in each of three major axes
5 Hz to 8 Hz at ±7.5 mm,
8 Hz to 500 Hz at 2 Gn

Humidity

BS EN 60068-2-30
Db Damp Heat Cyclic 20/55 ºC at 95% Relative Humidity 48 Hours

BS EN 60068-2-78
Cab Damp Heat Static 40 ºC at 93% Relative Humidity 48 Hours

Shock

BS EN 60068-2-27
Three shocks in each of three major axes
15 Gn in 11 ms

Degrees of Protection Provided by Enclosures

BS EN 60529
IP65 - From the front of the module when installed into a control panel (Integrated Gasket)

Product Variants

No product variants available